Bussmann Low-Peak CUBEFuse TCF10 Current Limiting Inrush Current Withstand Time Delay Fuse, 10 A, 600 V AC/300 V DC, 100/300 kA Interrupt, Class: CF, Square Body
Bussmann Series TCF10
Bussmann Low-Peak CUBEFuse TCF10 Current Limiting Inrush Current Withstand Time Delay Fuse, 10 A, 600 V AC/300 V DC, 100/300 kA Interrupt, Class: CF, Square Body
Out of Stockmore info
|
BrandBussmann Series
MFG #TCF10
Werner Part #23163
UPC051712614986
Out of Stockmore info
|
BrandBussmann Series
MFG #TCF10
Werner Part #23163
UPC051712614986
Product Description
Bussmann Low-Peak CUBEFuse Time Delay Fuse, Current Limiting Inrush Current Withstand, Series: TCF, 10 A, 600 V AC/300 V DC, 100/300 kA Interrupt, Class: CF, 10 s at 500% Response, Blade Terminal, Chassis/DIN Rail Mount, Square Body Type, Dual Element, Glass Filled Polyethersulfone, 1.88 in L x 0.75 in W x 1 in H Body Size
Attributes
Documents
Applications
Features
Attributes
Body Size1.88 in L x 0.75 in W x 1 in H
Body TypeSquare
ClassCF
Country of OriginSri Lanka
ElementDual
Interrupt Rating100/300 kA
ManufacturerEaton
MaterialGlass Filled Polyethersulfone
Mounting TypeChassis/DIN Rail
Response Time10 s at 500%
SeriesTCF
Terminal TypeBlade
Type / StyleCurrent Limiting Inrush Current Withstand
Commercial/Institutional Buildings/structures, Power Distribution and Control, Electrical Panel Boards, Machinery Disconnects, Industrial Control and Required Finger safe system Applications, Safety and Security Systems, Stationary Machinery and Equipment Outside Factory
Features
The world's first finger safe power fuse system
Smallest footprint of any class fuse including class J, CC, T and RK
The indicating version features easyID open fuse technology for faster troubleshooting and reduced downtime
Faster response to damaging faults to help reduce destructive thermal and magnetic forces
True dual element fuse construction with a minimum of 10 s time delay at 500% of rating
Long time delay minimizes nuisance circuit openings due to temporary overloads and transient surges
High 300 kA interrupt rating safely interrupts virtually any fault
No venting of arc or molten metal and gases during opening
Robust cycling and inrush current withstand
Low let through currents under fault conditions
Provides type 2 "no damage" in protection for IEC motors starters when properly sized
Easy selective co-ordination with any other Bussmann series Low-Peak class CC, J, L or RK1 fuse with simple 2:1 amp ratio between upstream and downstream fuses